Besides the integrated country software and DC disconnector, the SOLIVIA 3.3 has a maximum efficiency of 96.0 %.
Due to the wide input voltage range of 125 V to 540 V, the inverter are suitable for a broad range of photovoltaic installation types.
The SOLIVIA 3.3 from Delta can be used for any size of installation. It is particularly suitable for users who are looking for medium-sized solar installations.
Features
- Transformer with peak efficiency (96.0 %)
- Isolation of primary and secondary circuit
- Wide operating temperature ranges: -25 °C to +70 °C
- Full power up to 57 °C (without derating)
- RS485 (EIA485) communication interfaces
- Intelligent MPP tracking
- Suitable for indoor and outdoor applications (IP65)
- Without fan
| Input (DC) | Output (AC) | ||
| Max. recommended PV power (W) | 4000 | Nominal power (W) | 3300 |
| Nominal power (W) | 3630 | Max. power (W) | 3485 |
| Voltage range (V) | 125 ... 540 | Voltage range (V ) | 184 ... 264 * |
| MPP range (V) | 150 ... 450 | Nominal current (A) | 14.4 |
| Full power MPP range (V) | 150 ... 450 | Max. current (A) | 17.0 |
| Nominal current (A) | 13.3 | Nominal frequency (Hz) | 50 |
| Max. current (A) | 24.0 | Frequency range (Hz) | 47.0 ... 52.0 * |
| Stand-by power (W) | < 0.2 | Power factor | > 0.99 @ nominal power |
| Total harmonic distortion (THD) | < 3 % @ nominal power | ||
| General specification | Mechanical design | ||
| Model name | SOLIVIA 3.3 EU G3 | Size (L x W x D ) | 410 x 410 x180 mm? |
| Part number Delta | EOE46010190 | Weight (kg) | 21.5 |
| Max. efficiency (%) | 96.0 | Cooling | Convection |
| Efficiency EU | 94.8 | AC connector | Wieland RST25i3S |
| Operating temperature (°C) | -25 ... +70 | DC connector pairs | 3 Tyco Solarlok |
| Storage temperature (°C) | -25 ... +80 | Communication interfaces | 2 Harting RJ45/ RS485 |
| Humidity (%) | 0 ... 98 | DC disconnector | integrated |
| Display | black/white graphical LCD; 3 LEDs | ||
| Standards | Directives | ||
| Protection degree | IP65 | EMC | EN61000-6-2 |
| Safety class | 1 | EN61000-6-3 | |
| Configurable trip parameters | Yes | EN61000-3-2 | |
| Insulation monitoring | Yes | EN61000-3-3 | |
| Overload behavior | Current limitation, power limitation | ||
| Safety | EN60950-1; EN50178 | ||
| IEC62103; IEC62109-1 / -2 | |||
| Anti-islanding protection | DIN VDE 0126-1-1; RD 1663 | ||
| DK 5940 Ed.2.2; EN 50438 |